Features with all optional accessories:

  • Automatic Cold Junction Compensation
  • Field Adjustable Set and Reset
  • Plug-In Design for Fast Installation
  • Input LoopTracker® and Alarm Status LEDs
  • Alarm Test, Optional Reset Button

Applications:

  • Process Limit Backup Alarm
  • Temperature Alarm
  • Over, Under, Out-of-Range Alarm

The API 1220 G are factory configured for a thermocouple input and provide alarm contact outputs. Heavy duty relay contacts allow the module to directly control high capacity loads.

The API 1220 G contains two independent set and reset adjustments with two SPDT relay contact outputs. The alarm output can be factory configured for HI/HI, HI/LO, LO/HI or LO/ LO operation, normal acting or reverse acting. Top-accessible potentiometers are used to adjust each alarm trip and reset points.

LoopTracker and Alarm Status LEDs

API exclusive features include a LoopTracker LED that varies in intensity with changes in the thermocouple input signal. A two red/green bi-color alarm status LED visually indicate alarm status. These LEDs provide a quick visual picture of your process at all times.

Output Test/Reset

API’s exclusive functional test button can be used to verify the alarm and system operation. The output test button greatly aids in saving time during initial startup and/or troubleshooting. The HT latching option provides the additional function of unlatching the alarm when the reset button is pressed. The alarm will reset if the alarm condition not longer exists.

Specifications Table:

Input Most Thermocouple Types
Output One 8 Amp DPDT Relay or Two 8 Amp SPDT Relays
Thermocouple Input
  • Factory configured, please specify thermocouple type and temperature range in °F or °C
  • J, K, T, E, R, S, N, B, C, D, G, M, P
  • Full ANSI temperature ranges
  • Note: 100°F (55°C) is the recommended minimum span Consult factory if a smaller span is required
Cold Junction Compensation Automatic for specified thermocouple
T/C Burnout Protection Upscale burnout protection standard
T/C Current Less than 1.0 µA, including burnout sense
Relay Output
  • Two independent SPDT form C contact sets
  • Two set points, two 12 turn potentiometers, 0-100% span
  • Two reset points, two 12 turn potentiometers, 0-100% span
  • Factory configured alarm action
  • Standard: HI/LO alarm, non-latching, normal acting
  • Options: LO/LO, HI/HI, LO/HI alarms, latching, reverse acting
Relay Contact Rating
  • 8 A at 240 VAC resistive load or 30 VDC resistive load
  • 5 A at 240 VAC inductive load (cos f = 0.4)
  • 3.5 A at 30 VDC inductive load (L/R = 7ms)
  • See graph on other side for relay load ratings
  • Caution: Do not exceed socket voltage rating Use an RC snubber for inductive loads
Output Test/Reset Button Toggles relay(s) to opposite state when pressed
Response Time 300 milliseconds typical
Ambient Temperature Range and Stability
  • “10°C to +60°C operating ambient
  • Better than ±0.02% of span per °C stability, calculated, not tested
Housing
  • IP 40, requires installation in panel or enclosure
  • API 011 or API 011 FS socket
Sockets Socket mounts to 35 mm DIN rail or can be surface mounted
Power 115 VAC ±10%, 50/60 Hz, 2.5 W max