Home » Shop » hot sale » OPTO 22 – AD14T _ G1 10 Ohm RTD Analog Input, Isolated

OPTO 22 – AD14T _ G1 10 Ohm RTD Analog Input, Isolated

Original price was: $198.00.Current price is: $120.81.

Sale!

17 in stock

SKU: AD14T Category:

OPTO 22 – AD14T _ G1 10 Ohm RTD Analog Input, Isolated

Quick Specs:

  • G1 10 Ohm RTD Analog Input
  • Isolated

G1 I/O family

The AD14T is a 10 ohm copper RTD analog input with a nominal temperature range of -55 °C to 150 °C (-67 °F to 302 °F). This module provides a single channel of optically isolated RTD temperature-to-digital conversion with 4,000 Vrms of transient isolation.

This module is suitable for temperature measurements where the RTD probe is grounded or when ground loop currents exist.

Specifications:

 

AD10T2

AD14T

RTD Input

100 Ω platinum (α = 0.00385)

10 Ω copper

Nominal Temperature Range

– 50 °C to 350 °C

– 55 °C to 150 °C

Nominal Temperature Range

– 58 °F to 662 °F

– 67 °F to 302 °F

Over/Under Range

– 60 °C to 812 °C

N/A

Over/Under Range

– 140 °F to 1493 °F

N/A

Accuracy

± 0.4 °C

± 0.6 °C

Resolution

12 bits

12 bits

Response Time

full scale step change in 100 ms

full scale step change in 100 ms

Isolation Transient
  Input-to-Output
  Input-to-Analog Supply

 

4,000 VRMS
4,000 VRMS

 

4,000 VRMS
4,000 VRMS

Power Requirements

45 mA at +15 (+/- 0.25) VDC and 45 mA at -15 (+/- 0.25) VDC

35 mA at +15 (+/- 0.25) VDC and 35 mA at -15 (+/- 0.25) VDC

Temperature
  Operating

 

0 °C to 70 °C
– 25 °C to 85 °C

 

0 °C to 70 °C
– 25 °C to 85 °C

Agency Approvals CE; RoHS; UKCA CE; RoHS; UKCA