OPTO 22 – ODC5P _ Flat Pak output module, 5-60 VDC
OPTO 22 – ODC5P _ Flat Pak output module, 5-60 VDC
Quick Specs:
- Flat Pak output module
- 5-60 VDC
Because of their low profile, Flat Pak modules are ideal for user-designed printed circuit boards where the standard single-channel or Quad Pak modules do not provide an exact fit.
The ODC5P handles 5-60 VDC. This module is used for controlling or switching DC loads. The module provides up to 4000 V of optical isolation between field inputs and the logic side of the circuit.
Typical uses and applications include switching the following loads:
- DC relays
- DC solenoids
- DC motor starters
- DC lamps or indicators
Specifications:
|
|
OAC5P |
ODC5P |
|
Operating Voltage Range |
12 – 140 VAC |
5 – 60 VDC |
|
Line Voltage, Nominal |
120 VAC |
n/a |
|
Current Rating |
3 A @ 45 °C ambient 2 A @ 70 °C ambient |
3 A @ 45 °C ambient 2 A @ 70 °C ambient |
|
Off-state Leakage at Maximum Voltage |
5 mA, rms |
1 mA |
|
Logic Voltage, Nominal |
5 VDC |
5 VDC |
|
Logic Voltage Range (Vcc) |
2.5 – 8 VDC |
2.5 – 8 VDC |
|
Logic Pickup Voltage |
2.55 VDC |
2.5 VDC |
|
Logic Dropout Voltage |
1 VDC |
1 VDC |
|
Logic Input Current at Normal Logic Voltage |
12 mA |
12 mA |
|
Control Resistance (Rc in Schematic Diagram) |
220 Ohms |
220 Ohms |
|
One-second Surge |
n/a |
5 A |
|
One-cycle Surge |
80 A peak |
n/a |
|
Peak Repetitive Voltage |
500 V |
n/a |
|
Minimum Load Current |
20 mA |
n/a |
|
Operating Frequency |
25 – 65 Hz |
n/a |
|
Turn-on Time |
1/2 cycle maximum, zero voltage |
100 microseconds |
|
Turn-off Time |
1/2 cycle maximum, zero current |
750 microseconds |
|
DV/DT, Off-state |
200 V/microsecond |
n/a |
|
DV/DT, Commutating |
Snubbed for rated 0.5 power factor load |
n/a |
|
Output Voltage Drop Maximum Peak |
1.6 V |
1.6 V |
|
Operating Temperature |
– 30 to 70 °C |
– 30 to 70 °C |
|
Agency Approvals |
UL (E58169), CSA (35852) |
UL (E58169), CSA (35852) |
|
Warranty |
Lifetime |
Lifetime |